SUP-602S Intelligent signal isolator for voltage/current
-
Advantages
• Dielectric strength (leakage current 1mA, with test time of 1 minute):
≥1500VAC (among input/output/power supply)
• Insulation resistance:
≥100MΩ (among input/output/power supply)
• EMC: EMC conforms to IEC61326-3
• Power supply: DC 18~32V (typical value 24V DC)
• Full-load power:
Single-channel input, single-channel output 0.6W
Single-channel input, double-channel output 1.5W
-
Specification
• Allowed input signal:
DC: 0(4)mA~20mA;0mA~10mA
Other signal types may be customized as required, see the product label for details;
• Input impedance: about 100Ω
• Allowed output signal:
• Current: 0(4)mA~20mA;0mA~10mA
Voltage: 0(1) V~5V;0V~10V
Other signal types may be customized as required, see the product label for the specific signal types;
• Output load capacity:
0(4)mA~20mA:≤550Ω;0mA~10mA:≤1.1kΩ
0(1)V~5V:≥1MΩ; 0V~10V:≥2MΩ
Other load demands may be customized as required, see the product label for details.
• Distribution output voltage:
No-load voltage≤26V, full-load voltage≥23V
Accuracy of isolated transmission:
±0.1%F∙S(25℃±2℃)
• Temperature drift: 40ppm/℃
• Response time: ≤0.5s