Professional China Magnetic Flow Transmitter - SUP-110T Economic 3-digit Single-loop Digital Display Controller – Sinomeasure
Professional China Magnetic Flow Transmitter - SUP-110T Economic 3-digit Single-loop Digital Display Controller – Sinomeasure Detail:
-
Specification
Product | Digital Single-loop digital display controller |
Model | SUP-110T |
Display | Dual-screen LED display |
Dimension | C. 96*96*110mm D. 96*48*110mm E. 48*96*110mm F. 72*72*110mm H. 48*48*110mm |
Measurement accuracy | ±0.3%FS |
Analog output | Analog output—-4-20mA、1-5V(RL≤500Ω)、1-5V(RL≥250kΩ) |
Alarm Output | With upper and lower limit alarm function, with alarm return difference setting;Relay contact capacity: AC125V/0.5A(small)DC24V/0.5A(small)(Resistance C load) AC220V/2A(big)DC24V/2A(big)(Resistive load) Note: When the load exceeds the relay contact capacity, please do not directly carry the load |
Power supply | AC/DC100~240V (Frequency50/60Hz) Power consumption≤5W DC 12~36V Power consumption≤3W |
Use environment | Operating temperature(-10~50℃)No condensation, no icing |
Control precision | ±0.5℃ |
-
Introduction
Economic 3-digit Single-loop Digital Display Controller is in modular structure, easily operable, cost-effective, applicable in light industry machinery, ovens, laboratory equipment, heating/cooling and other objects in the temperature range of 0~999 °C. The instrument displays with dual row 3-digit numeric tube, with a variety of RTD/TC input signal types optional with an accuracy of 0.3%; 5 sizes optional, supporting 2 alarm functions, with transmission output. Optical isolation for input terminal, output terminal, a power supply terminal, 100-240V AC/DC or 12-36V DC switching power supply, standard snap-on installation, ambient temperature at 0-50 °C, and the relative humidity of 5-85% RH (no condensation).
Terminal Assignments and Dimensions:
(1) PV display window (measured value)
(2) SV display window
In measurement state, the display is defined by dis in the level-1 parameters; in parameters setting state, it displays the set value.
(3) The first alarm (AL1) and the second alarm (AL2) indicators, running lights (OUT), A/M indicators without effect
(4) Confirm key
(5) Shift key
(6) Down key
(7) Up key
Input signal type list:
Graduation Number Pn | Signal type | Measure range | Graduation Number Pn | Signal type | Measure range |
0 | TC B | 100~999℃ | 5 | TC J | 0~999℃ |
1 | TC S | 0~999℃ | 6 | TC R | 0~999℃ |
2 | TC K | 0~999℃ | 7 | TC N | 0~999℃ |
3 | TC E | 0~999℃ | 11 | RTD Cu50 | -50~150℃ |
4 | TC T | 0~400℃ | 14 | RTD Pt100 | -199~650℃ |
Product detail pictures:





Related Product Guide:
Our pursuit and enterprise goal is to "Always satisfy our customer requirements". We keep on to establish and style and design outstanding top quality goods for both our outdated and new prospects and realize a win-win prospect for our clientele likewise as us for Professional China Magnetic Flow Transmitter - SUP-110T Economic 3-digit Single-loop Digital Display Controller – Sinomeasure , The product will supply to all over the world, such as: Tajikistan, Turin, Slovakia, With the effort to keep pace with world's trend, we will always endeavor to meet customers' demands. If you want develop any other new products, we can customize them for you. If you feel interest in any of our products or want develop new products, please feel free to contact us. We are looking forward to forming successful business relationship with customers all over the world.