Ph Controller Dosing Manufacturer – SUP-PTU300 Turbidity meter – Sinomeasure
Ph Controller Dosing Manufacturer – SUP-PTU300 Turbidity meter – Sinomeasure Detail:
-
Specification
| Range | 0-20 NTU (31),0-1 NTU (30) |
| Operating voltage | DC 24V |
| Measurement | 90° scattering |
| Working mode | Continuous monitoring of drainage, intermittent automatic discharge |
| Zero drift | ≤±0.015 NTU |
| Value error | ≤±2% or ±0.015 NTU larger |
| Discharge mode | Automatic discharge |
| Calibration | Formalhydrazine standard liquid calibration (factory calibrated) |
| Water pressure | 0.1 Kg/cm3-8Kg/cm3, flow not exceeding 300 mL /min |
| Digital output | RS485Modbus protocol (baud rate 9600,8, N 、1) |
| Analog output | 4-20 mA |
| Storage temperature | -20℃-60℃ |
| Working temperature | 0-50℃ |
| Sensor material | Composite |
| Maintenance cycle | 6-12 months recommended (depending on site water quality environment) |
-
Introduction




Product detail pictures:
Related Product Guide:
We believe in: Innovation is our soul and spirit. Top quality is our life. Purchaser need is our God for Ph Controller Dosing Manufacturer – SUP-PTU300 Turbidity meter – Sinomeasure , The product will supply to all over the world, such as: Paris, Bulgaria, Bolivia, Our items have been obtained more and more recognition from foreign clients, and established long term and cooperative relationship with them. We`ll supply the best service for every customer and sincerely welcome friends to work with us and establish the mutual benefit together.
This supplier's raw material quality is stable and reliable, has always been in accordance with the requirements of our company to provide the goods that quality meet our requirements.